Dor-2100R : Door Controller with Mifare reader.

The Dor-2100R controller with Mifare card reader ,ensures that the Doors are normally closed and are locked.Unlocking any door causes the interlocked door to be incapable of being unlocked and hence prevents simultaneous operation of doors. Multi-Level Logic allows allows simultaneous use of the Change rooms and reduces hindrance to Man Movement. Dor-2100R units can be configured as Slave and used with Dwar series Door Manager to set up advanced Door Interlock system integrated with Access Control features.


  • Compact design and elegant snap fit bezel.
  • Contact Less operation : Mifare card Reader.
  • Easy Installation, minimum civil work and interconnecting cables.
  • Mounting: directly on Door Frame.
  • Auxiliary input for 3rd party Integration.
  • Special Functions : Privacy Logic,Free Access,Forced Lock.
  • Number of Doors Controlled: One.
  • Configurable as slave.

  • Alarms


  • Propped Door Alarm :Intermittent Beeps.
  • The Sounder activates when the door is unlocked/ open for more than 20 seconds : .
  • Forced Door Alarm :Continuous Beep
  • The Sounder activates when the door is forced open, without the operation of Door Release Button.
  • Emergency Alarm :Intermittent Beeps with dual colour indications
  • The sounder activates when Emergency situation is initiated.
  • Door not locked Alarm :Intermittent Beeps
  • The sounder activates when the door is not properly locked.

    Door Operations Modes


  • Access Denied:Local
  • Door is permanently locked when auxiliary input is momentarily activated and remains in lock condition until reset with second momentary signal.
  • Access Denied:Global
  • All Doors in the system are permanently locked when auxiliary input is momentarily activated and remains in lock condition until reset with second momentary signal.
  • Free Access:Local
  • Door is unlocked when auxiliary input is activated and resets only after auxiliary input is deactivated.
  • Free Access:Global
  • All doors in system are unlocked when auxiliary input is activated and resets only after auxiliary input is deactivated.
  • Emergency
  • All doors in system are unlocked and audio-visual alarm is activated.

    Timers


  • Door Release Timer (DRT)
  • The time for which the door to be in release condition when a valid external request (Door Release) or internal command (Cap sense Proximity is detected) is available. Default time is 5 seconds and can be configured using configuration utility.
  • Egress Time Delay (ETD)
  • The time delay duration between the request to release door command and releasing of the door. Default time is 0 seconds and can be configured using configuration utility.
  • Interlock Time Delay (ITD)
  • The time delay duration between the next release of the door after the previous release of the interlocked doors. Default time is 0 seconds and can be configured using configuration utility.
  • Lock Time Delay (LTD)
  • The time delay duration between Doors return to close condition and Lock energizing. Default time is 0 seconds and can be configured using configuration utility.